What is the difference between MAX, MIN, and AVG values of a power logger?
QThere are three values of MAX, MIN and AVG in PW3365-20's data. What is the difference?
A
The PW3365 calculates every 200ms internally without any gaps.The recording interval can be set from 1s to 60min.
For example, when recording in 10s intervals, there are 50 calculated values and the maximum, minimum and average values of all 50 data can be recorded.
If you set to save "AVG only", only the average values are saved. If you set "All", the maximum, minimum and avarage values are recorded.