CLAMP ON EARTH TESTER FT6380-50
Easy Pole Clamp-On Ground Resistance Tester with Super Slim Jaw
The FT6380-50 measures grounding resistance simply by clamping to multiple-grounded ground wires. No auxiliary grounding rod is needed, and there is no need to disconnect the ground wire from the grounding rod. The compact, low-profile sensor can be used to clamp ground wires with ease, and also provide AC current measurement functionality and can measure currents ranging from leakage current on the order of several mA to load currents of up to 60 A.
CAT IV 600 V
Easy! Just connect the optional Z3210 Wireless Adapter to your Hioki compatible instrument, to make it Bluetooth® ready.
Wirelessly connect Hioki-compliant instruments with a simple connection.
Transmit measured values to your tablet or smartphone.
Key Features
- Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
- Earth resistance measurement for multi-grounded systems
- Measure leak current with absolute certainty with highly sensitive 0.01 mA resolution (at 20.00 mA range)
- Measure load current up to 60.0 A range
- Clamp at the narrowest point
Model No. (Order Code)
FT6380-50 | Wireless Adapter Z3210 not included |
---|---|
FT6380-90 | Bundled with the Wireless Adapter Z3210 |
Multiple grounding can be easily checked with the clamps.
Measure multi-grounded systems
Clamp on the earth cable. The instrument has two cores for voltage injection and current measurement.
1. The voltage transducer injects a defined voltage into the multi-grounded system.
2. From the defined voltage and measured current, the total circuit loop resistance is calculated in the following equation.
Rx + 1/ [ (1/R1) + (1/R2) + (1/R3) + (1/R4) + ... ] = V/I
In a typical multi-grounded system, the parallel resistance value is small enough to be ignored and the equation as referred on the left can be simulated as follows.
Rx = V/I
Clamp at the narrowest point!
The dramatically slim 0.79 inch (20mm) jaws let you finish your job easily and efficiently.
Transfer data via Bluetooth® wireless communication
The new FT6380-50 is compatible with the Wireless Adapter Z3210 (optional).
When the Z3210 is installed, Bluetooth® wireless communication is enabled.
The measurement data can be transferred to the dedicated free application GENNECT Cross or your Excel® files and reports.
Easily transfer measurement data to an Excel® file
Excel® Direct Input function allows you to input measurement values directly and automatically into an Excel® file once the instrument's auto-hold function is activated. (Wireless Adapter Z3210 is necessary)
Instantly create reports by a free app (GENNECT Cross)
GENNECT Cross, a free app designed specifically for use with Hioki measuring instruments, lets you check and manage measurement results and create reports.
The software provides a range of functionality that helps manage data in the field, including photographing measurement sites, placing measurement results on photographs, and saving hand written memos.
In the previous model FT6381, only Android was supported in a separate app, but the new model supports GENNECT Cross, allowing users to create reports together with measurements from other instruments.
Optional Wireless Adapter Z3210 is necessary.
Alarm Function
Set the alarm to audibly and visually notify yourself that the resistance or current value exceeds the threshold.
High Accuracy and Repeatability
Well-designed magnetic shields eliminate the leakage flux between the two cores that often affect measurement accuracy.
LCD with beautiful back light
With the bright back light, you can easily read the measurement value even in dark locations.
Large storage capacity (up to 2,000 data)
You can store up to 2,000 measurement values in the field and recall them in your office later.
Basic specifications
Measurement principle | Instrument has two cores for voltage injection and current measurement. From the defined voltage and measured current, the total circuit loop resistance is calculated Note: For multi grounded systems only. In a multi-grounded system, the larger the number of grounding poles, the more accurate the measured value. |
|||||
---|---|---|---|---|---|---|
Earthing resistance range | 0.20 Ω (0.01 Ω resolution) to 1600 Ω (20 Ω resolution), 10 ranges, Zero suppression: Less than 0.02 Ω, Accuracy: ±1.5 % rdg. ±0.02 Ω |
|||||
AC Current range | 20.00 mA (0.01 mA resolution) to 60.0 A (0.1 A resolution), 5 ranges, Zero suppression: Less than 0.05 mA, Accuracy: ±2.0 % rdg. ±0.05 mA (30 Hz to 400 Hz, True RMS), Crest factor 5.0 or less (for the 60 A range, 1.7 or less) |
|||||
Maximum input current (Current measurement) | 100 A AC continuous, AC 200 A for 2 minutes or shorter (at 50 Hz/60 Hz, requires derating at frequency) | |||||
Maximum rated terminal-to-ground voltage | 600 VAC measurement category IV (anticipated transient overvoltage 8000 V) | |||||
Memory function | 2000 data | |||||
Alarm function | For resistance measurement and current measurement, Beeps when measured value is less than or greater than threshold. | |||||
Harmonic levels | [With Z3210 installed] Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio *Harmonics can be displayed with our free app GENNECT Cross. |
|||||
Other functions | Data hold, Backlight, Filter, Auto power save, Wireless communication (without Z3210 installed)) | |||||
Display | LCD, Max. 2,000 count Display refresh rate: Approx. 2 times/sec. | |||||
Dust-proof and waterproof | IP40 (EN60529) With Jaws Closed | |||||
Power supply | LR6 alkaline battery × 2 | |||||
Continuous operating time | Approx. 40 hours (25 Ω measurement, backlight off, without Z3210 installed) Approx. 35 hours (25 Ω measurement, backlight off, with Z3210 installed and using wireless communications) |
|||||
Maximum measurable conductor diameter | φ 32 mm (1.26 in) | |||||
Dimensions and mass | 73 mm (2.87 in) W × 218 mm (8.58 in) H × 43 mm (1.69 in) D, 620 g (21.9 oz) | |||||
Included accessories | Carrying case, Resistance check loop (1 Ω±2%, 25Ω±1%), Strap, LR6 alkaline battery × 2, Instruction manual |