CLAMP ON SENSOR 9661
For measuring load current, voltage output sensor
500 A AC
Hioki current sensors are best-in-class devices for use with power meters and PQAs. The 9661 is a 500 A AC clamp sensor with voltage output for measuring load current.
CAT III 600 V
Key Features
- For inverter devices or commercial power lines
- Measure up to 500 A
Model No. (Order Code)
9661 | For the PW3360/65, 3169, PW3198 and similar products |
---|
Note: Supports power quality analyzers, power meters and other data acquisition equipment with voltage input.
Basic specifications
Accuracy guaranteed: 1 year
Rated measurement current | 500 A AC | |||||
---|---|---|---|---|---|---|
Max. measurement current | Continuous 550 A (45 to 66 Hz) | |||||
Output rate | 1 mV AC/ A | |||||
Amplitude accuracy (45 to 66 Hz) |
±0.3% rdg. ±0.01% f.s. | |||||
Phase accuracy | ±0.5° (45 Hz to 5 kHz) | |||||
Amplitude frequency characteristics | Within ±1% at 40 Hz - 5 kHz (deviation from amplitude accuracy) | |||||
Max. rated voltage to earth | 600 V AC rms or less | |||||
Measurable conductor diameter | φ 46 mm (1.81 in) or less | |||||
Operating temperature and humidity | 0°C to 50°C (32°F to 122°F), 80% RH or less (no condensation) | |||||
Dustproofness and waterproofness | N/A | |||||
Dimensions and mass | 78 mm (3.07 in)W × 152 mm (5.98 in)H × 42 mm (1.65 in)D, 380 g (13.4 oz) Cord length 3 m (9.84 ft), Output terminal: BNC |