Japanese Chinese Korea
CLAMP ON SENSOR 9661, 9669 < Current Probes/Clamp Sensors < Products
For current input to be used with Power Meter (3169), Power Quality Analyzer (3196, 3197) For observing waveforms with the MEMORY HiCORDERs

CLAMP ON SENSOR 9661, 9669

CE
CAT III 600 V
DCL
Max. circuit voltage
600 V rms insulated wire
OVERVIEW  
For large current measurement, using with the HIOKI's instruments
  • For inverter devices or commercial power lines
  • Up to 500 A, or 1000 A measure
  • Basic specifications (accuracy guaranteed for 1 year)
      9661 9669
    Rated primary current AC 500 A AC 1000 A
    Output voltage AC 500 mV f.s. (AC 1 mV/A) AC 500 mV f.s. (AC 0.5 mV/A)
    Amplitude accuracy ±0.3 % rdg. ±0.01 % f.s. (45 to 66 Hz, f.s.= rated primary current) ±1.0 % rdg. ±0.01 % f.s. (45 to 66 Hz, f.s.= rated primary current)
    Phase accuracy ±0.5° (at 45 Hz - 5 kHz) ±1° (at 45 Hz - 5 kHz)
    Max. allowable input Continuous 550 A rms (at 45 - 66 Hz) Continuous 1000 A rms (at 45 - 66 Hz)
    Frequency characteristics 40 Hz to 5 kHz: ± 1.0% (deviation from accuracy) 40 Hz to 5 kHz: ± 2.0% (deviation from accuracy)
    Max. rated voltage to earth AC 600 V rms (insulated wire) AC 600 V rms (insulated wire)
    Core jaw dia. φ 46 mm (1.81 in) φ 55 mm (2.17 in) or 80 mm (3.15 in) × 20 mm (0.79 in) busbar
    Dimensions, mass 77 mm (3.03 in) W × 151 mm (5.94 in) H × 42 mm (1.65 in) D, 380 g (13.4 oz), cord length 3 m (9.84 ft) 99.5 mm (3.92 in) W × 188 mm (7.40 in) H × 42 mm (1.65 in) D, 590 g (20.8 oz), cord length: 3 m (9.84 ft)
    Note: In addition to the Power Quality Analyzer, can also be used as a current sensor with HIOKI's power meter and voltage input recorders.
    Use with these products
    PQA series MEMORY HiCORDER series CLAMP ON POWER HiTESTER series
    POWER QUALITY ANALYZER series MEMORY HiCORDER series CLAMP ON POWER HiTESTER series
    OVERVIEW