| Basic specifications |
 |
| Rated current |
500 A AC/DC (continuous 650 A) |
| Frequency band width |
DC to 20 kHz (±5 % f.s.) |
| Accuracy (at 45 to 66 Hz) |
±0.5 % rdg. ±0.05 % f.s., phase ±0.2 ° |
| Output rate (with the 9555-10) |
2 V/rated current range (waveform output, with the 9555-10) |
| Max. circuit voltage |
600 V peak (insulated wire), Note:The core, shield case, and electrical circuits are not insulated. |
| Core jaw dia. |
Ø 40 mm(1.57 in) |
| Power supply |
SENSOR UNIT 9555-10 (required) |
| Dimensions, mass |
220 mm(8.66 in)W × 103 mm(4.06 in)H × 43.5 mm(1.71 in)D, 860 g (30.3 oz), cord length: 3 m(9.84 ft) |
| Accessories |
CARRYING CASE 9375 (1) |
|
|