| Clamp Meters (Current Meters -for AC only, basic type-) |
CLAMP ON HiTESTER 3291 |
|
 |
|
 CAT III 600V CAT IV 300V |
 Max. rated voltage to earth
600V rms |
 |
|
 180°Open and Close system |
|
 |
 |
|
|
 |
 |
| Easily read measured values from all heights with the adjustable display |
 |
- Innovative flip clamp design
- Flip display to see measurement readings from any angle
- Max. 1000A, 3 ranges, Bar graph display
- Filter out high frequency noises for a clean signal
|
 |
| Basic specifications (Accuracy guaranteed for 1 year, or opening and closing of the clamp sensor 10,000 times) |
 |
| AC Current |
60.00/600.0/1000A, 3 ranges, 45Hz to 400Hz, true RMS rectified
Basic accuracy: ±1.5% rdg. ±5dgt. (50/60Hz, filter ON) |
| DC Voltage |
None |
| Frequency |
None |
| Crest factor |
2.8 (600A and under), 1.6 and under (600A over) |
| Filter function |
Cut off frequency 180Hz at filter ON (-3dB) |
| Output function |
None |
| Other function |
Flip-open mechanism (but still retaining proper orientation of display), Back light, Maximum value display, Data hold, Auto power off |
| Display |
Digital LCD, max. 6000dgt., 91 segments Display refresh rate: 2 times/s, (Bar graph display: 4 times/s) |
| Power consumption |
Coin type lithium battery (CR2032) × 1, Continuous use 10 hours |
| Core jaw dia. |
φ 30mm (1.18 in) |
| Dimensions, mass |
50mm (1.97 in) W × 136mm (5.35 in) H × 26mm (1.02 in) D, 90g (3.2 oz) |
| Supplied accessories |
Strap × 1, CARRYING CASE 9757× 1, Coin type lithium battery (CR2032, for trial purposes only) × 1, Quick start sticker × 1 |
|
|