| Good Design Product Selected by Ministry of International Trade and Industry (Japan) |
 |
| Clamp Meters (Current Meters -for AC only, basic type-) |
CLAMP ON HiTESTER 3280-10 |
|
 |
|
 |
CAT III 600 V (Current range) CAT II 600 V (Voltage range) |
 |
 |
|
 |
 |
|
|
 |
 |
| Easy operation ! |
 |
- 1000 A , clamp aperture: 33 mm(1.30 in) dia.
- Light 100 g(3.5 oz), and Slim 16 mm(0.63 in)
- Independent-opening double-lever design
- Slim body design, allows easy clamping even for narrow conductors
- No metal (iron core) exposure, ensuring enhanced safety
|
 |
| Basic specifications |
 |
| AC Current range |
42.00 to 1000 A AC, 3 ranges (±1.5 % rdg. ±5 dgt. at 50 or 60Hz), Average rectifier effective value |
| AC Voltage range |
4.200 to 600 V AC, 4 ranges (±2.3 % rdg. ±8 dgt. at 50 or 60Hz), Average rectifier effective value |
| DC Voltage range |
420.0 mV to 600 V DC, 5 ranges (±1.3 % rdg. ±4 dgt.) |
| Other functions |
Resistance: 420.0 to 42.00 M-ohm, 6 ranges, Accuracy: ±2.0 % rdg. ±4 dgt. (at 420 to 420 k-ohm range), Continuity: 420.0 ohm (Buzzer sounds at approx. 50 ohm or less) |
| Analog output |
None |
Frequency characteristics (at AC current / voltage) |
AC current: 50/60 Hz, AC voltage: 50 to 500 Hz |
| Display section |
Digital / LCD, maximum 4199 dgt. |
| Sampling rate |
2.5 times/sec or 1 times/3 sec |
| Max. circuit voltage |
600 V AC rms (insulated wire) |
| Power supply |
CR2032 (3 VDC) × 1, Continuous use 150 hours |
| Core jaw dia. |
Ø 33 mm(1.30 in) |
| Dimensions, mass |
57 mm(2.24 in)W × 175 mm(6.89 in)H × 16 mm(0.63 in)D, 100 g (22.44 oz) |
| Accessories |
TEST LEAD 9208 (1), CARRYING CASE 9398 (1) |
|
|