Measures the noise levels and frequencies on telecom, power and grounding lines
  • Easily view the noise current level in each band
  • Record noise level variations over time in each band
  • Measures noise current on earth lines easily
  • Hard to detect One-Shot noise with a spectrum analyzer or oscilloscope, are reliably captured
  • Data can be automatically saved to a PC Card, continuous long-term recording
Basic specifications (Accuracy guaranteed for 1 year)
Input terminal BNC (max. input voltage 5V peak), 5kHz to 100MHz (-3dB)
Measurement ranges [Current] 0.2mA, 2A, 20A (used with the 9754)
[Voltage] 10mV, 100mV, 1V
Band Path Filter characteristics Center frequency: 15k, 70k, 250k, 1M, 5M, 20M, 60MHz, 7 BPFs separates noise (fixed), measuring the peak value in each band
Monitor function Displays real-time peak-to-peak values in each frequency band on level meters, Refresh interval: 100ms
Logging function Records maximum peak-to-peak values in each frequency band at the specified recording interval to internal memory (16 days at 1sec interval to 2.5 years at 60sec interval)
Recording interval 1, 2, 5, 10, 20, 30, 60 sec
Functions Displays a time-series graph, Alarm function, Event mark function, External trigger
Interface LAN, RS-232C
Power consumption AC ADAPTER 9418-15 /30VA max., BATTERY PACK 9447 /Continuous use 1hour (20VA max,)
Dimensions and mass 203 (7.99in) W × 170 (6.69in) H × 52 (2.05in) D mm, 1.2kg (42.3oz)
Supplied accessories AC ADAPTER 9418-15 × 1, Carrying case × 1, Strap × 1, Ferrite clamp × 3, CD-R (DATA VIEWER for 3145 software, Communication commands manual, or other) × 1, Operating manual × 1, Operating guide × 1
9754 Basic specifications (Accuracy guaranteed for 1 year, 10,000 clamp open/close cycles)
Band width 1kHz to 100MHz (-3dB)
Rated current AC 10A (15A peak)
Amplitude accuracy ±3.0% rdg. ±0.001% f.s. (f.s. =10A, f=15kHz, with conductor centered in clamp)
Measurable conductor diameter up to f20mm (0.79 in)
Max. rated voltage to earth CAT II 600V, CAT III 300V (insulated conductor)
Dimensions and mass 176 (6.93in) W × 69 (2.72in) H × 27 (1.06in) D mm, 450g (15.9oz), Cord length 2m (6.56ft)
OVERVIEW OPTION DOWNLOAD CATALOG